Installation Procedure
Installation Procedure
• 1) SEG4
By SEG4 setting, Minimizing fan operation when thermostat is off.
- Fan operates for 20 seconds at an interval of 5 minutes in heat mode.
- Fan stops or operates Ultra low in Cooling when thermostat is off.
• 2) SEG8
Even if you set the Use of drain pump option to 0, it is utomatically set to 2 (the drain pump is used with 3
minute delay).
3) SEG11
Compensation of the wind-free fan RPM option adjusts 20 rpm per 1 step.
• 4) SEG18
If you set the Maximum filter usage time option to a value other than 2 and 6, it is automatically set to 2
(1000 hours).
Option SEG19 SEG20 SEG21 SEG22
Function Page
Individual control with
remote control
5)
Heating setting
compensation
6)
Reserved
Indication
and details
Indication Details Indication Details Indication Details
3
0 or 1 Indoor 1 0 Disuse
2Indoor 2 13.6F (2C)
3 Indoor 3
29F (5C)
4 Indoor 4
Option
SEG23 SEG24
Function
Setting the MDS Kit installation option
7)
Reserved
Indication
and details
Indication Details
0 Disuse (Soft Off+Hard off)
Standard
1 Off after 20 min. (Soft Off+Hard off)
2 Off after 40 min. (Soft Off+Hard off)
3 Off after 80 min. (Soft Off+Hard off)
Premium
4 Off after 20 min. (Soft Off+Hard off)
5 Off after 40 min. (Soft Off+Hard off)
6 Off after 80 min. (Soft Off+Hard off)
Standard
7 Off after 20 min. (Soft Off only)
8 Off after 40 min. (Soft Off only)
9 Off after 80 min. (Soft Off only)
Premium
A Off after 20 min. (Soft Off only)
B Off after 40 min. (Soft Off only)
C Off after 80 min. (Soft Off only)