Installation Procedure
• 5) SEG20
If you set the Individual control with remote control option to a value other than 0 to 4, it is automatically
set to 0 (Indoor 1)
• 6) SEG21
Default value of Heating setting compensation is 9°F(5জ).
• 7) SEG23
Soft Off: The indoor unit turns off its operation at the indicated time in the table for Installation Option after
its final motion detection. But, it turns on again if the MDS detects motion.
Hard Off: Designated time after SOFT OFF, it cannot turn on automatically when it detects motion. Users
should control to turn on the indoor unit with remote control, etc.
Changing the addresses and options individually
When you want to change the value of a specific option, refer to the following table and follow the steps in
Common steps for setting the addresses and options on page 23.
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Function Page Mode
Option mode to
change
Tens position of the
option number
Units position of
the option number
New value
Indication
and details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
0D
Option
type
0 to F
Tens
position
value
0 to 9
Units
position
value
0 to 9
New
value
0 to F
Example: Changing the Buzzer control (SEG17) option of the installation options to 1 disuse.
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Function Page Mode
Option mode to
change
Tens position
of the option
number
Units position
of the option
number
New value
Indication 0 D 2 1 7 1
CAUTION
• If your indoor units support both cooling and heating, the mixed operation (two or more indoor units operate
in different modes simultaneously) is not available when the indoor units are connected to the same
outdoor unit. If you set an indoor unit as the main indoor unit by using the remote control, the outdoor unit
automatically operated in the current mode of the main indoor unit.