Installation Procedure
Installation Procedure
3- phase
Model Outdoor unit Input current (A) Power supply
Indoor unit Outdoor unit Hz
Voltage range (V) Outdoor unit
Indoor unit Total MCA(A) MFA(A)
Rated Min. Max. Cooling Heating
AC071BN4PKG/EU
AC071BXAPNG/EU
50 380 to 415 342 456.5
16.1 16.1 1.5 17.6 17.6 17.6
AC071BN6PKG/EU
16.1 16.1 1.5 17.6 17.6 17.6
AC071BNMPKG/EU
16.1 16.1 2.5 18.6 18.6 18.6
AC071BNAPKG/EU
16.1 16.1 1.0 17.1 17.1 17.1
AC071BNCPKG/EU
16.1 16.1 2.5 18.6 18.6 18.6
AC100BN4PKG/EU
AC100BXAPNG/EU
16.1 16.1 1.5 17.6 17.6 17.6
AC100BN6PKG/EU
16.1 16.1 1.5 17.6 17.6 17.6
AC100BNMPKG/EU
16.1 16.1 2.5 18.6 18.6 18.6
AC100BNTPKG/EU
16.1 16.1 1.0 17.1 17.1 17.1
AC120BN4PKG/EU
AC120BXAPNG/EU
16.1 16.1 1.5 17.6 17.6 17.6
AC120BN6PKG/EU
16.1 16.1 1.5 17.6 17.6 17.6
AC120BNMPKG/EU
16.1 16.1 2.5 18.6 18.6 18.6
AC140BN4PKG/EU
AC140BXAPNG/EU
16.1 16.1 1.5 17.6 17.6 17.6
AC140BN6PKG/EU
16.1 16.1 1.5 17.6 17.6 17.6
AC140BNMPKG/EU
16.1 16.1 2.5 18.6 18.6 18.6
NOTE
1 Voltage range
Units are suitable for use on electrical systems
where voltage supplied to unit terminal is not
below or above listed range limits.
2 Maximum allowable voltage variation between phases
is 2%.
3 Wire size & type must comply with the applicable local
and national code.
Wire size: Based on the value of MCA.
Wire type: 60245 IEC57(IEC) or H05RN-F(CENELEC)
grade or more.
4 MFA is used to select the circuit breaker and the ground
fault circuit interrupter (earth leakage circuit breaker).
5 MCA represents maximum input current.
MFA represents capacity which may accept MCA
Abbreviations
MCA: Min. Circuit Amps. (A)
MFA: Max. Fuse Amps. (A)
6 This equipment complies with IEC 61000-3-12 provided
that the short-circuit power S
ϑʁ
is greater than or equal
to S
ϑʁ
(*2) at the interface point between the user’s
supply and the public system. It is the responsibility
of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if
necessary, that the equipment is connected only to a
supply with a short-circuit power S
ϑʁ
greater than or equal
to S
ϑʁ
(*2).
Model S
sc
[MVA]
AC071BXAPNG/EU 1.4
AC100BXAPNG/EU
AC120BXAPNG/EU
AC140BXAPNG/EU
1.6
ki]_TXX]]ZhTWXptjhjGyZYGwytGv|{kvvyl|luUGGGX[ YWYYTW\TY^GGG㝘㤸GXXa\Za[Z