19
English
Installation Procedure
Step 6 Connecting the refrigerant pipe
Items
Maximum allowable length
Single Installation DPM Installation
Applicable outdoor unit models
AC071BXAPKG
AC071BXAPNG
AC100BXAPKG
AC100BXAPNG
AC120BXAPNG
AC140BXAPNG
AC071BXAPKG
AC071BXAPNG
AC100BXAPKG
AC100BXAPNG
AC120BXAPNG
AC140BXAPNG
Total pipe length (L1+…+Ln+1+a+b)
- - 55 m 85 m
Main pipe (L1)
55 m 85 m 35 m 55 m
Max. distance among indoor units (D)
--10 m10 m
Max. length after branch
--15 m15 m
Max. height difference between
outdoor and indoor units (h1)
30 m30 m30 m30 m
Max. height difference among
indoor units(h2)
--0.5 m0.5 m
Max Pipe length difference among
indoor units after branch
[L2-L3 or L2-L4 or L2-L5 or a-b or
(a+L2)-(b+L4) or (a+L3)-(b+L5)]
--5 m5 m
"n" means the number of indoor unit connection of DPM.
indoor
indoor
indoor
outdoor
outdoor
outdoor
indoor
indoor
indoor
indoor
indoor
indoor
indoor
outdoor
L
1
L
1
L
2
L
2
D
D
D
D
h
2
h
2
L
3
L
3
L
4
L
4
L
5
L
1
a
b
D
L
1
L
2
L
3
h
1
h
2
h
1
h
1
h
1
n=1
n=2
n=3
n=4
ki]_TXX]]ZhTWXptjhjGyZYGwytGv|{kvvyl|luUGGGX` YWYYTW\TY^GGG㝘㤸GXXa\Za[[

Related product manuals