Setting an indoor unit address and installation option
Setting an indoor unit address (MAIN/RMC)
1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power
supply in the indoor unit.
2. The receiver kit should be connected to an indoor unit to receive option.
3. Before installing the indoor unit, assign an address to the indoor unit
according to the air conditioning system plan.
4. Assign an indoor unit address by wireless remote controller.
- The initial setting status of indoor unit ADDRESS(MAIN/RMC) is “0A0000-100000-200000-300000”.
- There is no need to assign extra ADDRESS for 1:1 installation between indoor unit and outdoor unit.
- Main address will be set automatically and manual address setting will be only available when outdoor unit option status is
set as ‘Manual address’
Option No. : 0AXXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation PAGE MODE Setting Main address
RESERVED RESERVED
The unit digit of an
indoor unit
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details
0A
0
No Main
address
0~3
A single
digit
1
Main
address
setting
mode
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation PAGE
RESERVED
Setting RMC address
RESERVED
Group channel(*16) Group address
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details
1
0
No RMC
address
RMC1 0~2 RMC2 0~F
1
RMC
address
setting
mode
CAUTION
t You can set the Main address from 0~3 range and if you input other numbers, communication error will occur.
t When A”~”F” is entered to SEG5~6, the indoor unit MAIN ADDRESS is not changed.
t If you set the SEG 3 as 0, the indoor unit will maintain the previous MAIN ADDRESS even if you input the option
value of SEG5~6.
t If you set the SEG 9 as 0, the indoor unit will maintain previous RMC ADDRESS even if you input the option value
of SEG11~12.