12
English
Outdoor unit installation
The outdoor unit must be installed on a rigid and stable base to avoid any increase in the noise level and vibration,
particularly if the outdoor unit is to be installed in a location exposed to strong winds or at a height, the unit must be xed to
an appropriate support(wall or ground).
Fix the outdoor unit with anchor bolts.
NOTE
The anchor bolt must be 20mm or higher from the base surface.
(Unit : mm)
620
940
330
360
384
Anchor bolt hole
660
880
310
340
364
Anchor bolt hole
Type A,B,C: AC030MXQFEC / AC036MXQFEC
AC042MXQFEC / AC048MXQFGC
AC060MXQFGC
Type D,E : AC018MXQFEC / AC024MXQFEC
543
790
285
319
343
Anchor bolt hole
Type F : AC012MXQFEC
CAUTION
Make a drain outlet around the base for outdoor unit drainage.
If the outdoor unit is installed on the roof, you have to check the ceiling strength and waterproof the unit.
Location of the compressor
Make sure that product is level during installation. Especially, product shouldn’t be tilted towards the
compressor.