Connecting the refrigerant pipe
Refrigerant piping system
Items
Maximum allowable length
Single installation
Applicable outdoor unit models AC012MXQFEC AC018MXQFEC
AC024MXQFEC
AC030MXQFEC
AC036MXQFEC
AC042MXQFEC
AC048MXQFGC
AC060MXQFGC
Main pipe (L
1) 20 m 30 m 50 m 75 m
Max. height dierence between
outdoor and indoor units (h
1)
15 m 20 m 30 m 30 m
Indoor
Outdoor
L1
H1
Indoor
Outdoor
L1
H1
f Temper grade and minimum thickness of the refrigerant pipe
Outer diameter [mm] Minimum thickness [mm] Temper grade
ø6.35 0.7
C1220T-O
ø9.52 0.7
ø12.70 0.8
ø15.88 1.0
ø15.88 0.8
C1220T-1/2H
OR
C1220T-H
ø19.05 0.9
ø22.23 0.9
Make sure to use C1220T-1/2H (Semi-hard) pipe for more than Ø19.05mm. In case of using C1220T-O (Soft)
pipe for Ø19.05mm, pipe may be broken, which can result in an injury.
CAUTION
The appearance of the unit may be dierent from the diagram depending on the model.
Make at least one round:
It will reduce noise and vibration
After connecting pipes with knock-out treatment, plug the space.
Following the pipe connection, make sure to proceed precisely to prevent interference with the internal parts.
CAUTION