Between Indoor unit and Outdoor unit Connection Cable Specications(Common in use)
Power supply
Communation Cable
Power supply Max/Min(V) Indoor Power Cable
, 220 - 240V, 50Hz ±10%
2.5mm² , 3wires 0.75mm² , 2wires
Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed exible cord (Code
designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC66 / CENELEC H07RN-F)
When installing the indoor unit in a computer room or net work room, use the double
shielded (Tape aluminum / polyester braid + copper ) cable of FROHH2R type.
1-phase terminal block specications
AC power : M5 screw AC power : M4 screw Communication : M4 screw
1(L) 2(N)
N
L
15 12
1(L) 2(N)
N
L
9.95 11.55
10.1
11.4
Communication : M3 screw
6.7
9.7
3-phase terminal block specications
AC power : M4 screw Communication : M4 screw
N
L3(T)
1(L) 2(N)
L2(S)
L1(R)
9.95 11.55
10.1
11.4
Connecting the cable