Samsung AM036TXMDCH - MCU Branch Part Setup Error - Connect an Indoor Unit to a Branch Part Not Being Used

Samsung AM036TXMDCH
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ƟθͱЇɵʪϑ˵ͱͱϩ˝
34 Samsung Electronics
ߤࣗߤࣗߢߡđAƸɵθɇʀ˵ΧɇθϩϑʪϩЇΧʪθθͱθࣔAͱʪʀϩɇÃʒͱͱθЇϩϩͱɇɵθɇʀ˵Χɇθϩͱϩɵʪ˝Їϑʪʒ
Outdoor unit
display
Indoorunit
display
Duct, Cassette (1/2 Way),Console, Celing Cassette (4/Mini4 Way) Wall-mounted (NeoForte)
Operation Defrost Timer Fan Filter/MPI Operation Defrost Timer Filter Operation Timer Turbo ߣߥঐ ߣߨ
㼼㾠 㼼㾠㾠㼼
࢘ : ON : Flash ×: OFF
Criteria • Occurs when MCU PIPE is turned off, yet an indoor unit is registered
Cause of
problem
• Indoor unit connection to the unused branch part
ߢࢋ ²ͱиϩͱʀ˵ʪʀ
Check the actual use of the branch part. If it is used, turn on the Dip switch for branch part setup. After completing resetting,
press the outdoor unit's K3 button to reset or turn off to restart.
MCU BOX #1
MCU PCB
OFF
MCU address setup
ON
Indoor unit
Indoor unit address
Branch part use setup
4 4 2 1 5 6
0
Branch A
4
B
C D E
5
F
62