ߤࣗߤࣗߣߨAЇθθʪϩʪθθͱθࢥťAͱЭʪθͱɇʒʪθθͱθ࣍kθθͱθAͱʒʪࡠkߥߧߣࡡkߥߩߥ࣎
ߢࢋ A˵ʪʀϩʪϑ
1) Check the power and restarting after power reset.
2) Check the outdoor unit installation and environments.
ߣ࣎A˵ʪʀ˙ϩ˵ʪͱЇϩʒͱͱθЇϩЭʪθϩʪθť9θʪɇϩʪʒиθʪϑ
are disconnected. Check the installation environment.
3) Check for indoor unit installation environment.
4) Check for open service valve.
ߣࢋ A˵ʪʀΧθͱʀʪʒЇθʪ
Error CODE Error description Related model
E462 Outdoor unit total current error AM****XMDC* series
E484 Outdoor unit PFC overload error AM****XMDC* series
Yes
Check the outdoor unit installation and
environment o Check for normal operation
oEnd service
1. Check for wire disconnection related to outdoor
unit inverter PBA.
2. Remove the obstacles on outdoor unit air inlet
and secure enough space.
3. Remove the obstacles on outdoor unit air outlet
and secure enough space.
Check the indoor unit installation and environment
o Check for normal operation o End service
1. Remove obstacles on air inlet and secure
enough space.
2. Remove obstacles on air outlet and secure
enough space.
No
Is the outdoor unit installed correctly?
Change the outdoor unit inverter PBA and check for
normal operation o End service
Yes
No
Is the indoor unit installed correctly?
Yes
Change the compressor.
No
Yes
Turn off the power and turn it
on again after 30 seconds.
Open the valve.
No
Is the service valve completely open?
Is the compressor operating normally?
[AM
✳✳✳✳