Samsung Electronics 57
ߤࣗߤࣗߤߡĮϩ˵ʪθϑ
ߢࢋ AͱΧθʪϑϑͱθǤϩʪθθͱθࡠkߥߧߦ
If the compressor operation is abnormal, change the compressor and check for normal operation
Ã˙ϩ˵ʪʀͱΧθʪϑϑͱθͱΧʪθɇϩͱϑͱθɇࡡʀ˵ʪʀϩ˵ʪɇϑϑʪɵцɵʪϩиʪʪ˵ʪɇϩϑΧɇϩʪɇʒ˙ϩ˵ʪθʪϑͱΧθͱɵʪࡡʀ˵ɇ˝ʪϩ˵ʪ
inverter PBA
ߣࢋAЇθθʪϩϑʪϑͱθʪθθͱθࡠkߥߧߩ
EEPROM Uploading at indoor main PBA, Check if PCB operation is normal
ߤࢋĮƟťʪθθͱθࡠkߥߨߢ
Error occurs when the EEPROM DATA in the outdoor unit main PBA and inverter PBA is different from each other. Check the
model name and EEPROM code to use it
ߥࢋUAЭͱϩɇ˝ʪϑʪϑͱθʪθθͱθࡠkߥߧߪ
Error occurs when DC LINK value is not normal (DC LINK VOLTAGE: 280~320V)
Check the value of DC link when error occurs and check the reactor disconnection
ߦࢋ²ʪɇϩϑϩʪΧʪθɇϩЇθʪʪθθͱθࡠkߥߨߥࡡkߦߡߡ
Error occurs when heat sink of the inverter PBA exceeds rated range
Clean and remove any dust and other foreign substances on the outdoor unit and then check the connection between heat sink
and inverter PBA
Make sure grease is applied properly and screw is firmly fixed
ߧࢋÃΧЇϩʀЇθθʪϩϑʪϑͱθʪθθͱθࡠkߥߩߦ
Detect the input sensor while the set is in stop status to check if there’s any problem
When error occurs, turn on/off the power for number of time and if same error occurs while the power is off, change the inverter
PBA
ߨࢋ kkťŵĮđθʪɇʒࢥиθϩʪʪθθͱθࡠkߥߨߡ
Error occurs when there is no EEPROM data in the set. Check the model name and insert EEPROM for corresponding model or
load the EEPROM data.