30
Refrigerant pipe installation
Insulating the Y-join, liquid & gas side connecting pipe
Attach the insulation provided with the Y-joint to the insulation purchased privately without a gap. Wrap the connected
part with insulation (Purchased privately) of a thickness of at least 10mm (3/8).
Use insulation that should be able to handle an interior temperature of over 12C(24F). Wrap the Y- joint with
insulation of a thickness of at least 10mm (3/8).
Fix securely without any gap.
Provided
insulation
Fix securely
without any gap.
Pipe insulation
(Purchased privately)
Pipe insulation
(Purchased privately)
150mm
(5.90”)
Y-joint
Thickness of the insulation (Purchased privately)
should be at least thicker than 10mm (3/8”).
Insulation tape
(Purchased privately)
Pipe insulation
(Purchased privately)
Pipe
Attach the adhesive insulation
tape to the pipe as shown in the
picture after insulating the pipe.
AM0@@FXMDCH_IM_EN_03408A(1).indd 30 2013-03-04 오후 4:28:25