Samsung Electronics 41
3-8. Suction temperature sensor is detached from the sensor holder on the pipe. (E-269)
Outdoor unit Display E-269
Indoor unit Display
Duct, Cassette (1 / 2Way), Console, Ceiling
Operation Defrost Timer Fan Filter / MPI
××
Cassette (4Way / Mini 4Way)
Operation Defrost Timer Filter
×
Duct, Cassette (1/2 Way), Console, Ceiling
Operation Timer Turbo 24°C 27°C
× ×
: ON
: Flash ×: OFF
Judgement Method
t+VEHNFOU.FUIPE%JGGFSFODFPGTVDUJPOUFNQFSBUVSFPGDPNQSFTTPSTUBSUJOH
verge and suction temperature that is on present operation : If less than 2 °C for
30 minutes to keep.(Judgment at heating operation only)
Cause of problem t4VDUJPOUFNQFSBUVSFTFOTPSCSFBLBXBZEFGFDUJWF
Yes
Is Suction sensor
and sensor Holder accurately
attached?
Is Suction sensor
resistance value reasonable?
(Refer to E231 )
Complete.
Re-insert sensor OR and re-attach sensor holder.
Defective sensor : Replace sensor.
Yes
No
No