Samsung Electronics 234
Piping Diagram
DSH (Discharge Super Heat) protection
ƒ Purpose
Prevent liquid compression to protect the system and compressors.
ƒ Concept
The compressor Suction Super Heat (SH) is raised to increase the DSH.
- DSH = Compressor discharge temp. – High pressure saturation temp.
- The
compressor discharge temperature is defined during DSH protection control :
Min { Max(Tdis_comp1, Ttop_comp1), Max(Tdis_comp2, Ttop_comp2) }
ƒ Control specifications in detail
- The target su
perheat changes to 6 K if the DSH is 10 K or lower.
(QWKDOS\
3UHVVXUH
3K'LDJUDP
$I WHU'6+SURWHFWLRQ
%HIR UH'6+SURWHFWLRQ
'6+LQFUHDVH
6+LQFUHDVH
1RUPDO2SHUDWLRQ



'6+.
First heating release : the target SH is 3 K if in this state for 30 sec
Second heating release : SH release occurs 2 min after the first release
if the DSH is below 15 K
First cooling release : the target SH is 3 K if in this state for 30 sec
Second cooling release : SH release occurs 2 min after the first release if
the DSH is above 10 K
- If in this state for 30 sec,
Cooling : Indoor unit EEV Target SH 6 K
Heating : Main EEV Target S
H 6 K
7-3 Functions (cont.)
7-3-2-5 Protective control (cont.)
7-3-2 Control (cont.)

Table of Contents