Samsung Electronics 246
Piping Diagram
Drain Pump Control
ƒ Purpose
Discharge the condensate stagnating in the indoor unit's drainage plate to prevent the condensate from overflowing
indoor units.
ƒ Concept
If the
amount of condensate stagnating in the drainage plate reaches a certain level where it may overflow, the Float soft-
ware detects this a
nd activates the drain pump to discharge the condensate to the outside via the hose.
ƒ Control specifications in detail
Condition(s) required to use the mode : The Drain Pump
Option is used, or the model name
(Rem_Opt) is set to 1-Way, 2-Way, or 4-Way
Drain Pump ON : (Cooling or Auto cooling or Dehumidifying mode ON) and
(Ou
tdoor Comp ON) and (Indoor unit Thermo-ON)
Thermo-ON
Thermo-OFF
Outdoor Comp ON
Outdoor Comp OFF
Detected by the Float S/W
Not detected by the Float S/W
Drain Pump ON
Drain Pum
p OFF
Cooling or Auto cooling or
Dehumidifying mode
Drain Pump OFF : (Operation OFF) or (Indoor unit Thermo OFF)
Thermo-ON
Thermo-OFF
Outdoor Comp ON
Outdoor Comp OFF
Detected by the Float S/W
Not detected by the Float S/W
Drain Pump ON
Drain Pum
p OFF
If 3-min delay option (Rem_Opt) is on
Cooling or Auto cooling or
Dehumidifying mode
ƒ Notes
The drain pump activates if the Float S/W operates in heating mode
Outdoor Comp ON
Outdoor Comp OFF
Detected by the Float S/W
Not detected by the Float S/W
Drain Pump ON
Drain Pump OFF
Cooling or Auto cooling or
Dehumidifying mode
7-3 Functions (cont.)
7-3-2-6 Indoor unit control (cont.)
7-3-2 Control (cont.)