Samsung Electronics 268
Key Options
8-4 How to check the view mode using a tact switch
(cont.)
AM080/100/120/200FXWA66 (cont.)
Optional item Input unit SEG1 SEG2SEG3SEG4 Function of the option Remarks
Setting longpiping
condition
(Setting is
unnecessary
if high-head
condition is set.)
Main 0 9
00 Disable (Factory defau
lt)
0 1Long piping level 1
When equivalent length of
farthest indoor unit from
the outdoor unit is between
100~170 m
02 Long piping level 2
When equival
ent length of
farthest indoor unit from the
outdoor unit is over 170 m
Energy saving/
rapid cooling
setting
(B type PBA)
Main 1 0
00 Disable (Factory default)
0 1E
nergy saving mode
Energy saving mode triggers
when the room temperature
reaches desired temperature
while operating in cooling or
heating mode.
02 Rapid cooling
This function increases cooling
speed.
Disable Main 11
00 Disable
This function is not applicable
for this model
0 1 Disable
Expand
operational
temperatu
re
range for cooling
operation
Main 1 2
00 Disable
0 1Enable
Channel address Main 1 3
A U
Automatic setting
(Factory default)
Address for classifying the
product from upp
er level
controller (DMS, S-NET 3, etc)
0 ~ 15
Manual setting for channel
0~15
Disable Main 14
00 Disable
This function is not applicable
for this model
0 1 Disable
Circula
tion water
flow control
Individual1 5
00 Disable (Factory default)
0 1 7-10 V
When variable flow control
valve is applied
02 5-10 V
03 3-10 V
Forced quiet
mode (Disuse)
M
ain 1 600 Disused option
High-speed
operation
(B type PBA)
Main 1 7
00 Disable (Factory default)
High-speed operation
0 1Enable
Max. capacity
restriction
(B type PBA)
Main 18
00 En
able
Maximum cooling capacity
restriction
0 1 Disable
Gasleak
Pumpdown
(B type PBA)
Main 1 9
00 Disable
Leaked refrigerant collection
0 1Enable
Note 1)
Circulation
fluid flow setting
(B type PBA)
Individual 20
00 Water
Circulation fluid flow setting0 1 Anti-freeze solution 1
02 Anti-freeze solution 2
Disable Ma
in 2 1
00 Disable
This function is not applicable
for this model
0 1 Disable
Emergency
operation for
indoor unit
communication
error (B type PBA)
Main 22
00 Disabled (Factory default)
Whe
n set, emergency operation
is possible even if an indoor
communication error occurs.
0 1
Indoor high humidity condition
(operating for up to 12hours)
02
In
door low humidity condition
(operating for up to 24hours)
Note 1) Anti-freeze solution 1: Freezing point of anti-freeze must be below -8 ˚C. (Minimum temperature of entering water: - 5˚C)
Anti-freeze solution 2: F
reezing point of anti-freeze must be below -15 ˚C. (Minimum temperature of entering water: - 10˚C)