Test Operation
Samsung Electronics 287
6) Compressors
∙ What to inspect: Compressor's operation electric current
∙ Error code: None (“NG” is only indicated in the result report)
∙ How to determine error: Compare
the compressor's operation electric current and the reference electric current.
∙ Perform inspection according to the steps shown below.
Ŷ Precautions
- To replace a component or inspect the PBA, be sure to cut off the power supply first.
If inspection must be performed with the power supply on, exercis
e extra care to prevent electric shock.
Are the specifications
of the power supplied to the outdoor unit
and the cable connection
normal?
Is the compressor's
operation electric current (CT1, C
T2) value 0
when the compressor is
not active?
Is the compressor's
phase-to-phase (U-V, V-W, W-U) resistance
lower than 2Ω?
Install an ammeter, a
nd then
perform Trial Operation (cooling/heating)
- See the instructions on Key operation modes.
Is the value
indicated by the ammeter
identical with the compressor
's operation
electric current (CT1, CT2)
value?
Is the operation cycle
normal?
Is the
compressor's operation electric current
(CT1, CT2) value normal?
Pe
rform Auto Trial Operation again.
Take corrective measures.
Replace the compressor.
Perform Trial Operation (cooling/heating)
- See the instructions on Key operation m
odes.
Replace the inverter PBA.
Replace the compressor.
Replace the inverter PBA.
Take corrective measures.
Cut off the power supplied to the
outdoor unit.
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
9-1 Auto Trial Operation (cont.)
9-1-3 How to resolve NG items (cont.)