EasyManua.ls Logo

Samsung AM200FXWANR - Input; Output Current Sensor Error

Samsung AM200FXWANR
295 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Samsung Electronics 135
4-3-46 Input / Output Current sensor error
Outdoor unit display
INVERTER1 PBA(Input Current sensor)
INVERTER2 PBA(Input Current sensor)
INVERTER1 PBA(Output Current sensor)
INVERTER 2 PBA(Output Current sensor)
OUTDOOR FAN PBA (FAN1 Output Current sensor)
OUTDOOR FAN PBA (FAN2 Output Current sensor)
Judgment Method
∙ Sensor Output detection : Judged as an error if the detected value is More than 4.5V or less than 0.5V
Cause of problem
∙ Input voltage defective
∙ PBA voltage sensing circuit defective
Power Off
Replace Inverter PBA.
Yes
No
Is Power connection
accurately connected?
E485 or E385?
E468 or E368?
Power Cable re-connection.
1.
Cause of problem
4-3 Appropriate Measures for Different Symptom (cont.)

Table of Contents