Piping Diagram
Emergency operation for compressor malfunction
ƒ Purpose
Perform emergency operation until servicing if there is compressor failure when using more than one compressor.
ƒ Concept
Faulty compressors are d
isabled and turned off.
ƒ Control specifications in detail
Disabled compressors are excluded from capacity distribution, heat treatment of winding wire, protective control, and
self-diagnosed error
detection.
ƒ Notes
- The performance may degrade if this option is changed.
- Make sure to return the option to the default value after servicing the compr
essor.
- Error E560 will be triggered if all the compressors on outdoor units are disabled.
(The SVC V/V must be closed for outdoor units if modules are
installed and all the compressors on a single
outdoor unit are disabled.)
Setting Outdoor Seg1 Seg2 Seg3 Seg4Emergency operation for compressor malfunction
Individual 00
00 Disabled (Default)
0 1 Set compressor 1 as malfunction state
02 Set compressor 2 a
s malfunction state
7-3 Functions (cont.)
7-3-3-1 Field Setting
7-3-3 Others