Piping Diagram
Samsung Electronics 189
No Part Name Abbreviation Symbol Function
21
4Way Valve
(Solenoid valve-4Way)
V_4W
It determines the cooling / heating operation mode.
(The valve signal when the heating operation is ON)
22
Discharge Temp. Sensor
(Thermistor-Discharge pipe)
T_D
Measure the temperatur e of the compressor discharge pipe.
It is mainly used to protect the compressor.
23
Suction Temp. Sensor
(Thermistor-Suction pipe)
T_S
Measure the temperatur e of the compressor suction line.
It is used to determine the suction superheat of the com
pressor.
24
Cond Out Temp. Sensor
(Thermistor-C ond Out)
T_CO
Measure the liquid pipe temperature of the heat exchanger.
Used to enter in defrosting operation and escape judgment.
25
EVI In Temp. Sensor
(Thermistor-EVI In)
T_EI
Measure the temperatur e of the
intercooler inlet pipe (EVI EEV side).
It is used to determine the superheat of the EVI In / Out.
26
EVI Out Temp. Sensor
(Thermistor-EVI Out)
T_EO
Measure the temperatur e of the intercooler outlet pipe (EVI EEV side).
It is
used to determine the superheat of the EVI In / Out .
27
Liquid Tube Temp. Sensor (Thermistor-
Liquid pipe)
T_L
Measure the temperatur e of the outdoor liquid pipe.
It is used to determine the supercooling.
28
Comp. Top Temp. Sensor
(Therm
istor-Compressor Top)
T_CT
To measure the surface temperature of the compressor Top Cover.
It is mainly used to protect the compressor.
29
Ambient Temp. Sensor
(Thermistor-Ambient)
T_A Measur e the temperature of the outdoor air.
30
Water Temp. Sensor
(Thermistor-Water)
T_W Water
- Cycle component Symbol and Function (cont.)
7-1 Piping Diagram (cont.)