Piping Diagram
Samsung Electronics 201
7-3-2-1 Actuator
7-3-2 Control
Compressor – Capacity control
ƒ Purpose
Adjust the compressor operation frequency through fuzzy control. This adjusts the capacity according to load in cooling
or heating mode.
ƒ Concept
The compressor fr
equency is adjusted through fuzzy control to enable cooling according to the target low pressure.
The compressor frequency is adjusted through fuzzy control to
enable heating according to the target high pressure.
ƒ Control specifications in detail
In cooling case
The capacity of a compressor is controlled by assuming the target pressure during c
ooling operation.
Measure pressure using the pressure sensor (low pressure sensor) installed in the outdoor unit.
In case that the measured value
is lower than the target pressure, lower the operating capacity of the compressor consid-
ering that the operating capacity is higher compar
ed to load.
In case that the measured value is higher than the target pressure, raise the operating capacity of the compressor consid-
ering th
at the operating capacity is lower compared to load.
7-3 Functions (cont.)