Piping Diagram
Samsung Electronics 231
Discharge temperature protection
ƒ Purpose
Prevent abnormal discharge temperature to protect the system and compressors.
ƒ Concept
Two-phase refrigerant is injected into compressors to decrease the discharge temperature.
The compressor frequency is lowered to decrease
the discharge temperature.
ƒ Control specifications in detail
- The compressor frequency is controlled according to the discharge temp, as shown below.
1st step EVIEEV Open : E
VIEEV is forcibly opened.
2nd step EVIEEV Open : The current frequency is fixed. (It is possible to lower the frequency if necessary)
3rd step Hz d
own : The frequency is forcibly lowered by 5Hz at specified intervals.
4th step HP down : The frequency is forcibly lowered by 1Hz every second.
5th
step Comp trip : Compressors stop and an error is triggered (E416).
&RPSUHVVRU7ULS(
'LVFKDUJH7HPSHUDWXUH  &RPSUHVVRU7ULS UHOHDVH
+]+ROGDUHD
+]'RZQDUHD
+3'RZQDUHD
1RUPDORSHUDWLRQ
+]+ROGUHOHDVH
+]' RZQUHOHDVH
+3'RZQUHOHDVH
7HPSHUDWXUH
'LVFKDUJH&RPS7RS
(9,((9IRUFHGFR QWURO
(9,((9FRQWUROUHOHDVH






7-3 Functions (cont.)
7-3-2-5 Protective control (cont.)
7-3-2 Control (cont.)