Piping Diagram
Samsung Electronics 251
Current restriction rate
ƒ Purpose
Reduce the electric current used for operation.
ƒ Concept
The max electric current (50% - 100%) is restricted.
ƒ Control specifications in detail
- The maximum current for outdoor units is restri
cted according to the current ratio that was configured while in cooling
or heating mode.
- See "Maximum current limit (total)" for details.
ƒ Notes
- When
current restriction option is set, cooling and heating performance may decrease and power of
outdoor will increase.
- To set no restriction, make sur
e to contact an expert install service provider.
Outdoor units operate with an abnormal current.
This may affect the power and operation. The electri
c current protective control remains on to protect the units.
Input unit Seg1 Seg2 Seg3 Seg4 Current restriction rate
Individual 02
0 0 100% (default)
0 1 95%
0 2 90%
0 3 85%
0 4 80%
0 5 75%
0 6 70%
0 7 65%
0 8 60%
0 9 55%
1 0 50%
1 1 No re
striction
Oil collection interval
ƒ Purpose
The oil return cycle is shortened by half.
ƒ Concept
- Oil recovery is performed at the halved oil return interval.
- See "Oil return operation" for
details on oil return operation specifications.
ƒ Notes
Change the option if an oil leak occurs. Performance may degrade if the option is not changed.
Make sur
e to restore the original value after refilling the oil.
Input unit Seg1 Seg2 Seg3 Seg4 Oil collection interval
Main 0 4
00 Standard (default)
0 1 Shorten the interval by 1/2
7-3 Functions (cont.)
7-3-3-1 Field Setting (cont.)
7-3-3 Others (cont.)