Key Options
1. Outdoor unit’s address setting – K7 & K8
: In module installation each ODU will have different address.
Address Main Unit Sub1 Unit Sub 2 Unit Sub3 Unit
Setting
K7 : on, K8 : on
K7 : on, K8 : off K7 : off, K8 : on K7 : off, K8 : off
2. Maximum capacity restriction for cooling - K6
: To restrict excessive capacity increasing for cooling operation.
(Just leave it on position, Used to be expressed with Anti-dewing operation)
Function Use(default) No use
Setting
K6 : on
K6 : off
- In humid condition, its easy to be dewing on the surface of indoor units panel because of cold draft from the indoor unit.
So system will li
mit compressor maximum operable frequency to prevent dewing problem.
This doesnt mean shortage of cooling capacity but better reliability.
8-3 Outdoor unit option switch settings (cont.)
Sub3
Sub2
Sub1
OF1, OF2
Main
F1, F2