Samsung Electronics 264
Key Options
Ŷ Push Button Type
Setting outdoor unit option switches : B TYPE PBA
Start
Outdoor unit address.
Quantity of indoor units
Quantity of MCUs.
Save
Main unit?
Heat recovery?
Yes
Yes
Yes
No
No
StepButton Display Description Note
Outdoor unit address
Step1
Outdoor unit
display
Setting required -
Step2
Press (K1+K2)
for 2 seconds
Unit address
for module
combination
00: Main unit
K4 x 1 time
01: Sub1 unit
K4 x 2 times
02: Sub2 unit
K4 x 3 times
03: Sub3 unit
Step3
If it is main unit, go to step4.
Otherwise, press K2 button for 2 seconds to save & exit
(system will be reset)
Quantity of indoor units
St
ep3 Press K1
Ready to set -
Step5
K2 x n times
Tens digit (0 ~ 6)
Ex) 03 : 3 units
64 : 64 units
K4 x n times
Ones digit (0 ~ 9)
Step6
If it is heat recovery model, go to step 7.
Otherwise, press K2 button for 2 seconds to save & exit
(system will be reset)
Qua
ntity of MCUs * Heat recovery model only
Step7 Press K1
Ready to set -
Step8
K2 x n times
Tens digit (0 ~ 1)
Ex) 03 : 3 units
16 : 16 units
K4 x n times
Ones digit (0 ~ 9)
* K4: Press for 2 seconds - automatic detection of MCUs' quantity
Step9Press K1
Ready to set
00 : Heat pump system
01 : Heat recoverysystem
Step10 Press K4
Ones digit (0 ~ 1)
Step9K2: long
Save Restart
* Press K1 for 2 seconds to exit without save regardless of setting step.