Key Options
Samsung Electronics 267
8-4 How to check the view mode using a tact switch (cont.)
AM080/100/120/200FXWA66
Optional item Input unit SEG1 SEG2SEG3SEG4 Function of the option Remarks
Emergency
operation for
compressor
malfunction
Individual 00
00 Disabled (Factory default)
E560 will occur wh
en all
the compressors are set as
malfunction state.
0 1
Set compressor 1 as
malfunction state
02
Set compressor 2 as
malfunction state
Cooling capacity
c
orrection
Main 0 1
00 7-9 (Factory default)
Targeted evaporation
temperature [°C].
(When low temperature value is
set, discharged air temperature
of the
indoor unit will decrease)
0 1 5-7
02 9-11
03 10-12
0 4 11-13
0 5 12-14
06 13-15
Capcity correction
for heating
Main 02
00 2.8 (Factory default)
Targeted high pressure [MPa].
(When low pr
essure value is set,
discharged air temperature of
the indoor unit will decrease)
0 1 2.5
0 2 2.6
0 3 2.7
0 4 2.9
0 5 3.0
06 3.1
0 7 3.2
0 8 3.3
Current restriction
rate
Individual 03
00
100% (Factory default)
0 195 %
02 90 %
03 85 %
0 480 %
0 5 75 %
06 70 %
07 65 %
0 8 60 %
0 9 55 %
1 0 50 %
11 No restriction
Oil collection
interval
Main 0 4
0 0 Factory default
0 1 Shorten the interval by 1/2
Disable Main 0 5
00 Disable
This function is not applicable
for this model
0 1 Disable
DisableIndividual 06
00 Disable
This function is not applicable
for this model
0 1 Disable
Disable
Main 07
00 Disable
This function is not applicable
for this model
0 1 Disable
02 Disable
03 Disable
Setting highhead
condition
Main 0 8
00 Disable (Factory default)
0 1
Level 1 of height diffe
rence
type 1 (Indoor unit is lower
than outdoor unit)
When outdoor unit is over 40 ~
80 m above the indoor unit
02
Level 2 of height difference
t
ype 1 (Indoor unit is lower
than outdoor unit)
When outdoor unit is over 80 m
above the indoor unit
03
Height difference type 2
(Outdoor unit is l
ower than
indoor unit)
When indoor unit is over 30 m
above the outdoor unit