4-3-17 Outdoor Temperature Sensor Error
1.
Cause of pr oblem
Is the outdoor
temperature sensor connector (CN43)
connected to PCB?
Did the resistance
value significantly stray from the following
temperature table?
After separating the outdoor temperature
sensor connector from the PCB, measure
the resistance value between the terminals.
Restart operation after replace the PCB
Restart operation after connecting
the connector to the PCB.
Replace this since it is the defective of
the outdoor temperature sensor itself.
Yes
No
No
CN43 (7, 8)
Yes
TemperatureC)
70
60
50
40
30
20
10
0
-10
Resistance (K)
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
Resistance value measure part
OUT
OUT
Outdoor unit
display
Indoorunit
display
Duct, Cassette (1/2 Way),Console, Celing Cassette (4/Mini4 Way) Wall-mounted (NeoF orte)
Operation Defrost Timer F an F ilter/MPI Operation Defrost Timer Filter Operation Timer Turbo
24 27
◑×××
×
◑×
×
×
◑×
: ON : Flash ×: OFF
Judgment
Method
 Refer to the judgment method below.
Cause of
problem
Outdoor temperature sensor Open/Short is defective.