INSTALLING THE OUTDOOR UNIT
E-35
Electrical Work
1 The supply voltage must be the same as the rated voltage of the air conditioner.
2 Prepare the power souce for exclusive use with the air conditioner.
3 Use 15 amperes time delay fuse or circuit breaker.
When using the special NFB, use the NFB to bear the capacity of the
air conditioner.
Otherwise, the shot circuit in the NFB may be occur.
Model
Power supply
Power cable
Assembly cable
Operating current
Starting Current
Power consumption
AS12
✴✴
VC
208-230V~/60Hz Single phase
6A
33A
1280W
AS09
✴✴
VA
115V~/60Hz Single phase
8 A
45A
880W
10
3
AS07
✴✴
VA
115V~/60Hz Single phase
6 A
34A
670W
10
3
Auxiliary Circuit Breaker
N L 1 2 3
N L E
Outdoor
unit
Distribution
board
conduit kit
Auxiliary
power
s/w
Auxiliary circuit breaker should be installed near outdoor unit so that each
access is possible.
Main/outdoor power supply cable are connected to upper/lower terminal of
auxiliary circuit breaker.
It is necessary that the conduit kit for power supply to the outdoor unit be
installed between auxiliary power S/W and the outdoor unit.
(the conduit kit is optional)
3G AWG14
4G AWG14 + 1G AWG18