Product Feature and Specifications
Samsung Electronics2-20
Indoor Unit (cont.)
■ Duct type (Built-in)
Model
Power supply
Remark
Performance
Power
Piping connections
Set Size
Function /
Option
Cooling
✻
1)
Heating
✻
2)
Model
Type
Output
Air flow rate(Cool/Heat)
-
-
Liquid(Flare)
Gas(Flare)
Drain
Capacity
Sound Level
✻
3)
Fan motors
Running current
Power input
Refrigerant Control
Net weight
Shipping weight
Net dimension (WxHxD)
Shipping dimension(WxHxD)
Auto restart
Auto change over
Centralized controller (On/Off)
Group/Individual control for R/C
Troubleshooting by L.E.D
Auto swing (Up/Down)
Max. installation ceiling height
Drain pump
AVMBH020EA4 AVMBH026EA4 AVMBH035EA4 AVMBH052EA4 AVMBH070EA4
1, 220-240~, 50
7,000
2.0
7,500
2.2
37/34
OSME-414SAC(S304)
Sirocco
39
8.2/8.7
0.5
110
6.35
12.7
27
31
550x300x800
747x378x911
Yes
No
Yes(Option)
Yes(Option)
Yes
No
310
Yes(Option)
9,000
2.6
10,000
2.9
40/37
OSME-414SAC(S304)
Sirocco
42
9.2/9.7
0.55
120
6.35
12.7
27
31
550x300x800
747x378x911
Yes
No
Yes(Option)
Yes(Option)
Yes
No
310
Yes(Option)
12,000
3.5
13,000
3.8
41/38
OSME-414SAC(S304)
Sirocco
44
10/10.5
0.57
125
6.35
12.7
27
31
550x300x800
747x378x911
Yes
No
Yes(Option)
Yes(Option)
Yes
No
310
Yes(Option)
18,000
5.2
19,000
5.6
43/40
OSME-974SAC(S306)
Sirocco
53
16.5/17
0.76
150
9.52
15.88
38
44
1,020x300x800
1,214x378x911
Yes
No
Yes(Option)
Yes(Option)
Yes
No
310
Yes(Option)
24,000
7.0
26,000
7.6
45/42
OSME-974SAC(S306)
Sirocco
63
18.8/19.3
0.9
180
9.52
15.88
38
44
1,020x300x800
1,214x378x911
Yes
No
Yes(Option)
Yes(Option)
Yes
No
310
Yes(Option)
VP25, external diameter 32, internal diameter 25
EEV(Electronic Expansion Valve)
Heat pump
Btu/h
kW
Btu/h
kW
dB
-
-
W
m
3
/min
A
W
mm
mm
mm
kg
kg
mm
mm
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
mm
Yes/No
ø, V, Hz
✳ 1) Nominal cooling capacities are based on :
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, Equivalent refrigerant piping : 10m(horizontal)
✳ 2) Nominal heating capacities are based on :
- Indoor temperature : 20˚C DB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 10m(horizontal)
✳ 3) Noise level acquired in a dead room, so actual noise level may be different depending on the installation
conditions.