4-10
Installation
Caution :
• Test operation is disabled when the chamber “A” is on after initialization of wired remote controller.
• The communication time between wired remote controller and indoor unit is required for 2 seconds. If any one of set is ON, be sure to
put it off by pressing the ON/OFF button and start the TEST operation after 35 seconds at minimum.(The communication time with all
chambers : 16 x 2 seconds = 32seconds)
• For the reservation operation, the communication time between all 16 chambers is required for 64 seconds due to the increase of
communication data.
• The first digit (MSB) of error code displayed during the group operation stands for the address of SET where the error occurs.
Startup of group operation
• Put off the power of SET.
Adjust the addresses of digital switch of indoor
unit PCB to “0”~”15”, respectively.
• Put on the option switch SW2 of wired remote
controller PCB.
• Put on the power of SET.
• On the wired remote controller display, the digits
“00” “11” “22” are displayed up to “FF”.
After “FF” display, the wired remote controller is
automatically set to the preserved operation
status of indoor unit of chamber “A”.
• If the current SET of chamber “A” is ON, put the
set off by pressing the ON/OFF button.
Only at the SET off of chamber “A”, the TEST mode
is enabled.
• Press the TEST BUTTON of wired remote
controller for more than 3 seconds.
• If the SET is operating for 3 minutes through
forced cooling operation, the SET is off after 2
minutes.
• The Error occurring in the TEST operation
displays in the wired remote controller display
window and is referred to the following table.
Error Code
*1
*5
*6
*9
*A
*C
*D
Meaning
Indoor unit room thermistor error
Indoor pipe thermistor error
Outdoor unit thermistor error
Float switch open error
Indoor unit outdoor unit communication error
Wired remote controller indoor unit
communication error
Outdoor unit pipe thermistor error
Checking Area
• Indoor unit thermistor exist or not disconnected
• Indoor unit PCB
• Indoor unit pipe thermistor
• Indoor unit PCB
• Outdoor unit thermistor
• Outdoor unit PCB
• Drain pump, float switch
• Drain system
• Dip SW2 of indoor unit main PCB
(If drain pump is not installed, SW2 and SW4
shall be at OFF position.)
• Indoor unit Outdoor unit communication cable
• Indoor unit PCB, outdoor unit PCB
• Wired remote controller indoor unit
communication cable
• Indoor unit main PCB
• Outdoor unit pipe thermistor
• Outdoor unit PCB
Duct-ADH1800E-2-1 4/12/00 5:44 PM Page 4-10