Indoor Units
II-102
8
8
Ceiling
8-5. PCB connector lay-out
1 2 3 4
5
6 7
8
9
10111213
14
17 15
18 16
A CB
A
B
No.
SW01 SW02
S/W
Main Address Setting
(00~63)
FUNCTION
SW03 SW04
SW03
Address of
Interface
Module
Channel 0~2
SW04
Group Address
(RMC) for
Centralized
Control 0~F
No. CN # COLOR FUNCTION
1 CN71 Blue AC 230V Input
2 CN74 Yellow Drain Pump
3 CN75 Black Ventilator
4 CN73 White Fan Motor
5 CN32 White
DC12V for Wired Remote Controller
6 CN31 Red
Communication with
Outdoor Units (COM1)
7 CN33 Blue
Communication with Wired
Remote Controller (COM2)
8 CN91 White Display
9 CN81 Red
Error Check, Indoor unit Operation
10 CN42 White Eva-Out Sensor
11 CN41 White Room Sensor, Eva-In Sensor
12 CN83 Red External Contact Control
13 CN51 Black Float Switch
14 CN61 Blue Louver
15 CN62 Blue EEV
16 CN10 Black MICOM Download
17 CN11 Red Trans-Out (AC 17V)
18 CN72 White Trans-In (AC 230V)
C
No. S/W FUNCTION ON OFF
K1 - - -
K2 Centralized Controller Not use Use
K3 RPM Up N/A N/A
K4 Optional Drain Pump N/A N/A
K5 Heating Thermo-off +2°C +5°C
K6 Filter Signal Display 1,000hrs 2,000hrs
K7 Hot Water Coil N/A N/A
K8 Electrical Heater N/A N/A
K9 Min. EEV Step at Heating Fixed 80 step 0 or 80 step
K10
Priority of Indoor unit Display
Slave
on Wired Remote Controller
(Default)
Master
K11 External Contact Control Not use Use
K12 - - -
chapter2_Indoor units(052~107) 3/14/08 22:15 Page 102