I-38
5
5
DVM design process
H4
H3
H2
L
H1
Piping length : L + [the longest pipe out of (A, B, C, D)]
Piping height : The highest pipe out of (H1, H2, H3, H4)
Maximum level difference : H4
The actual capacity of outdoor unit : 47.5kW
The sum of capacity of all indoor units: 52.9kW
5) Calculate the actual capacity of each outdoor unit
Ô The actual capacity of each outdoor unit is as follows:
Ô Zone A : AVXWVH036 47.5kW x 3.6kW/52.9kW = 3.23kW
Zone B : AVXDSH071 47.5kW x 7.1kW/52.9kW = 6.38kW
Zone C : AVXCMH056 47.5kW x 5.6kW/52.9kW = 5.03kW
Zone D : AVXC4H071 47.5kW x 7.1kW/52.9kW = 6.38kW
Zone E : AVXDSH112 47.5kW x 11.2kW/52.9kW = 10.06kW
Zone F : AVXFHT071 47.5kW x 7.1kW/52.9kW = 6.38kW
Zone G : AVXC4H112 47.5kW x 11.2kW/52.9kW = 10.06kW
Each indoor unit capacity
the sum of capacity of all indoor units
Actual capacity of outdoor unit x
5-2. DVM design process example (Cooling)
1. products(01~41) 3/14/08 22:01 Page 38