EasyManua.ls Logo

Samsung DVM PLUS III HR - Page 733

Samsung DVM PLUS III HR
748 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VI-31
I
NSTALLATION
SEG 1 SEG 2, 3, 4
Push 1
st
time Outdoor capacity 1 Ex) 16 HP Off, 1, 6
Push 2
nd
time Digital comp loading time 2 Ex) Loading 13 sec Off, 1, 3
Push 3
nd
time High pressure (kg/cm
2
) 3 Ex) High pressure 15.2 (kg/cm
2
) 1, 5, 2
Push 4
th
time Low pressure (kg/cm
2
) 4 Ex) Low pressure 4.3 (kg/cm
2
) 0, 4, 3
Push 5
th
time Discharge temperature of compressor 1 5 Ex) 87˚C 0, 8, 7
Push 6
th
time Discharge temperature of compressor 2 6 Ex) 87˚C 0, 8, 7
Push 7
th
time Discharge temperature of compressor 3 7 Ex) 87˚C 0, 8, 7
Push 8
th
time CT sensor value of compressor 1 8 Ex) 2A 0, 0, 2
Push 9
th
time CT sensor value of compressor 2 9 Ex) 2A 0, 0, 2
Push 10
th
time CT sensor value of compressor 3 A Ex) 2A 0, 0, 2
Push 11
th
time Suction temperature B Ex) -5 ˚C -, 0, 5
Push 12
th
time Cond_out temperature C Ex) 35 ˚C 0, 3, 5
Push 13
th
time Liquid tube temperature D Ex) 35 ˚C 0, 3, 5
Push 14
th
time Oil temperature sensor on oil balancing pipe E Ex)
35 ˚C
0, 3, 5
Push 15
th
time Sump temperature of compressor 1 F Ex) 35˚C
0, 3, 5
Push 16
th
time Ambient air temperature G Ex) 35˚C
0, 3, 5
Push 17
th
time EVI_in temperature H Ex) 35˚C
0, 3, 5
Push 18
th
time EVI_out temperature I Ex) 35˚C
0, 3, 5
Push 19
th
time Main EEV1 step J Ex) 2000 steps
2, 0, 0
Push 20
th
time Main EEV2 step K Ex) 2000 steps
2, 0, 0
Push 21
th
time EVI EEV step L Ex) 300 steps
3, 0, 0
Push 22
th
time HR EEV step M Ex) 300 steps
3, 0, 0
Push 23
th
time Fan step ( SSR or BLDC ) N Ex) 13 steps
Off, 1, 3
Push 24
th
time Version
K4 Key function
Display LED
Note : LED display alphabet
SEG 1 SEG 2 SEG 3 SEG 4
06_Installation(02~45) 3/15/08 4:34 Page 31

Table of Contents

Other manuals for Samsung DVM PLUS III HR

Related product manuals