26
Selecting installation location
8. If the product installed within 500m of seashore,
- Standard model (AM✴✴✴MXVAFC/AZ) : Special anti-corrosion treatment is required.
- Corrosion resistance model (AM✴✴✴MXVAFCAAZ) : Special anti-corrosion treatment is recommended.
࢜ Please contact your local SAMSUNG representative for further details.
Sea
Sea
Sea breeze
Sea breeze
Outdoor
unit
Outdoor
unit
Outdoor unit
Protection wall should be constructed with a solid material that can block the sea
breeze and the height and width of the wall should be 1.5 times larger than the size of
the outdoor unit. (You must secure more than 700mm(28inch) of space between the
protection wall and the outdoor unit for air circulation.)
Sea
Sea breeze
Outdoor
unit
Outdoor unit
Protection wall
t System air conditioner may cause static noise when listening to AM stations. Therefore, select an installation location
for indoor unit where electrical wiring can be done while keeping certain distance from a radio, computer and stereo
equipment.
- Especially, keep the unit at least 3m(9.84inch) away from the electrical equipment in an area with weak
electromagnetic waves and put the main power cable and communication cables in a separately installed
protection tube.
- Make sure that there is no equipment that generates electromagnetic waves. If not electromagnetic waves may
cause problem to the control systems which may lead to air conditioner malfunction. (Example: Remote control
sensor of the indoor unit may not receive the signal very well, due to ballast stabilizer of the lighting equipment.)
t In regions with heavy snowfall, make sure to install the outdoor unit where there is no concerns of direct snowfall on
the outdoor unit. Also, build higher base support so that accumulated snow does not block the air inlet or the heat
exchanger.
t R-410A refrigerant is a safe, nontoxic and nonflammable refrigerant. However, if the place holds any concerns for
exceeding dangerous level of refrigerant concentration in case of refrigerant leakage, extra ventilation system is
required.
t When you install the outdoor unit in a high places such as roof, install fence or guardrail around it. When there is no
fence or guardrail, service person could fall.
t Do not install the product in places where corrosive gases such as sulfur oxides, ammonia, and sulfurous gas are
produced. (e.g. Toilet outlet, ventilation opening, sewage works, dyeing complex, cattle shed, sulfuric hot spring,
nuclear power plant, ship etc.) When installing the product in those places, contact an installation specialty store as the
copper pipe and brazing part will need additional corrosion proof or anti-rust additive to prevent corrosion.
t Make sure to keep any inflammable materials (such as wooden materials, oil etc.) around the outdoor unit. When
there's fire, those inflammable material will easily catch the fire and may pass it on to the product.
t Depending on the condition of power supply, unstable power or voltage any cause malfunction of the parts or control
system. (At the ship or places using power supply from electric generator...etc)
CAUTION