EasyManua.ls Logo

Samsung DVM S AM MXVAFC Series - Automatic Refrigerant Amount Detection Function

Samsung DVM S AM MXVAFC Series
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
96
Automatic refrigerant amount detection function
This function detects amount of refrigerant in the system through refrigerant amount detection operation
Start
Press the Tact switch "K2" 5
times
Check the amount of refrig
er
ant
Judge the amount of refrigerant
Judgment on the amount of
refrigerant: Normal /
Excessive /
Insufficient
Judgment not
available
Judgment not
available
Connect S-Net Pro Judge the amount of refrigerant
Judgment on the amount of
refrigerant: Normal /
Excessive /
Insufficient
Satisfy the temperature condition Satisfy the temperature condition
Check the amount of refrig
er
ant
Input S-CHECKER signal
Check stability Check stability
End
Yes
No No
Yes
After refrigerant amount detection is finished, if you see “K9 Ed” on the display and cannot check the refrigerant amount
from the S-net pro and S-checker, it means insufficient degree of supercooling.