83
ENGLISH
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Emergency
operation for
compressor
malfunction
Individual 0 0
0 0 Disabled (Factory default)
E560 will occur when all
the compressors are set as
malfunction state.
01
Set compressor 1 as
malfunction state
02
Set compressor 2 as
malfunction state
Cooling capacity
correction
Main 0 1
00
7-9 (Factory default in case
of A type PBA)
Targeted evaporation
temperature [°C].
(When low temperature value is
set, discharged air temperature of
the indoor unit will decrease)
01
5-7 (Factory default in case
of B type PBA)
0 2 9-11
0 3 10-12
0 4 11-13
0 5 12-14
0 6 13-15
Unused Option Main 0 2 0 0 Unused Option Unused option by this model
Current restriction
rate
Individual 0 3
0 0 100% (Factory default)
When restriction option is set,
cooling performance may
decrease.
0 1 95 %
0 2 90 %
0 3 85 %
0 4 80 %
0 5 75 %
0 6 70 %
0 7 65 %
0 8 60 %
0 9 55 %
1 0 50 %
1 1 No restriction
Oil collection
interval
Main 0 4
0 0 Factory default
0 1 Shorten the interval by 1/2
Unused Option Main 0 5 0 0 Unused Option Unused option by this model
Fan speed
correction for
outdoor unit
Individual 0 6
0 0 Factory default
0 1 Increase fan speed
Increase the outdoor unit's fan
speed to maximum value
t Do not use
this option in
an ambient
temperature over
54 °C. Failing to do
so may overheat the
fan motor, causing it
to stop operating.
CAUTION