85
ENGLISH
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Unused option Main 1 5 0 0 Unused option Unused option by this model
Unused option Main 1 6 0 0 Unused option Unused option by this model
Speed operation Main 1 7
0 0 Disabled (Factory default)
Enabling this setting will
command the air conditioner to
cool faster at initial start-up.
However, this function will not
work when High-head condition
setting or Long-piping condition
setting is enabled.
0 1 Enabled
Max. capacity
restriction
(B type PBA)
Main 1 8
0 0 Enabled (Factory default)
Restrict excessive capacity
increase when operating indoor
units with small capacity
0 1 Disabled
Gasleak
Pumpdown
(B type PBA)
Main 1 9
0 0 Disabled (Factory default)
If the gas leak occurred it should
be entered in the pumpdown
operation.
0 1 Enabled
Unused option Main 2 0 0 0 Unused option
Unused option by this model
LA KIT option
(B type PBA)
Main 2 1
0 0 Disabled (Factory default)
Set when LA KIT is installed.
0 1 Enabled
Emergency
operation for
indoor unit
communication
error (B type PBA)
Main 2 2
0 0 Disabled (Factory default)
When set, emergency operation
is possible even if an indoor
communication error occurs.
01
Indoor high humidity
condition (operating for up
to 12hours)
02
Indoor low humidity
condition (operating for up
to 24hours)
There is a risk of water leakage during emergency operation for indoor unit communication error. Please be careful when
using it.