87
ENGLISH
t After installing the product, be sure to perform leak tests on the piping connections. After pumping down
refrigerant to inspect or relocate the outdoor unit, be sure to stop the compressor and then remove the
connected pipes.
- Do not operate the compressor while a valve is open due to refrigerant leakage from a pipe or an unconnected
or incorrectly connected pipe. Failure to do so may cause air to flow into the compressor and too a high
pressure to develop inside the refrigerant circuit, leading to an explosion or product malfunction.
WARNING
K2 (Number of
press)
KEY operation Display on segment
1 time Refrigerant charging in Cooling mode “K” “5” “BLANK” “BLANK”
2 times Trial operation in Cooling mode “K” “6” “BLANK” “BLANK”
3 times Pump down all units in Cooling mode “K” “7” “BLANK” “BLANK”
4 times Trial operation in Cooling mode “K” “8” “BLANK” “BLANK”
5 times Checking the amount of refrigerant
“K” “9” X X (Display of last two digits may differ
depending on the progress)
6 times Discharge mode of DC link voltage “K” A “BLANK” “BLANK”
7 times Unused “K” “B “BLANK” “BLANK”
8 times Forced oil collection “K” “C” “BLANK” “BLANK
9 times Inverter compressor 1 check “K “D” “BLANK” “BLANK”
10 times Inverter compressor 2 check “K” “E” “BLANK” “BLANK”
11 times Fan 1 check “K” “F” “BLANK” “BLANK
12 times Fan 2 check “K” “G” “BLANK “BLANK”
13 times
A type PBA End key operation -
B type PBA Unused
“K” “H” X X
14 times B type PBA End key operation -
During "Discharge mode of DC link voltage", voltage of INV1 and INV2 will be displayed alternately.
Even when the outdoor unit power is off, it is dangerous when you come in contact with inverter PCB and fan PCB since
they are charged with high DC voltage.
When pressing K2 key 9 to 12 times without inverter checker, error code can be displayed on segment even though the
outdoor unit is normal.
When replacing/repairing the PCB, cut-off the power and wait until the DC voltage is discharged before replacing/
repairing them. (Wait for more than 15 minutes to allow it to discharge naturally.)
When there were error, 'Dicharge mode of DC link voltage' may not have been effective. Especialy if error E464 and E364
have been occured, power element might be damaged by fire and therefore, do not use the 'Discharge mode of DC link
voltage'.
K3 (Number of
press)
KEY operation Display on segment
1 time Intialize (Reset) setting Same as initial state