Essential
2. Specification
14
Type DVM S DVM S DVM S
Model Name AM160MXVDGH/ET AM180MXVDGH/ET AM200MXVDGH/ET
Outdoor unit module 1 - - AM100MXVDGH/ET
Outdoor unit module 2 - - AM100MXVDGH/ET
Outdoor unit module 3 - - -
Outdoor unit module 4 - - -
Wiring
connections
Transmission Cable mm
2
0.75 0.75 0.75
Remark -
F1, F2 F1, F2 F1, F2
Power supply intake -
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
Refrigerant Type -
R410A R410A R410A
Factory Charging kg
8.4 8.4 5.5 x 2
tCO
2
e
17.54 17.54 22.97
Sound Sound Pressure Cooling dB(A)
63 64 61
Heating dB(A)
67 67 63
Sound Power dB(A)
83 84 82
External
Dimension
Net Weight kg
253.0 255.0 197.0 x 2
Shipping Weight kg
273.0 275.0 204.0 x 2
Net Dimensions (WxHxD) mm
1,295 x 1,695 x 765 1,295 x 1,695 x 765 (880 x 1,695 x 765) x 2
Shipping Dimensions (WxHxD) mm
1,363 x 1,887 x 832 1,363 x 1,887 x 832 (948 x 1,887 x 832) x 2
Operating
Temp. Range
Cooling
-5 ~ 48 -5 ~ 48 -5 ~ 48
Heating
-25 ~ 24 -25 ~ 24 -25 ~ 24
NOTE
Specification may be subject to change without prior notice.
Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.