ENGLISH-76
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Energy saving/
rapid cooling
setting
(B type PBA)
Main 1 0
0 0 Disable (Factory default)
0 1 Energy saving mode
Energy saving mode triggers
when the room temperature
reaches desired temperature
while operating in cooling or
heating mode.
0 2 Rapid cooling
This function increases cooling
speed.
Disable Main 1 1
0 0 Disable
This function is not applicable
for this model
0 1 Disable
Expand
operational
temperature
range for cooling
operation
Main 1 2
0 0 Disable
0 1 Enable
Channel address Main 1 3
A U
Automatic setting (Factory
default)
Address for classifying the
product from upper level
controller (DMS, S-NET 3, etc)
0 ~ 15
Manual setting for channel
0~15
Disable Main 1 4
0 0 Disable
This function is not applicable
for this model
0 1 Disable
Circulation water
ow control
Individual 1 5
0 0 Disable (Factory default)
0 1 7-10 V
When variable ow control
valve is applied
0 2 5-10 V
0 3 3-10 V
Forced quiet
mode (Disuse)
Main 1 6 0 0 Disused option
High-speed
operation
(B type PBA)
Main 1 7
0 0 Disable (Factory default)
High-speed operation
0 1 Enable
Max. capacity
restriction
(B type PBA)
Main 1 8
0 0 Enable
Maximum cooling capacity
restriction
0 1 Disable
Gasleak
Pumpdown
(B type PBA)
Main 1 9
0 0 Disable
Leaked refrigerant collection
0 1 Enable
Setting outdoor unit option switch and key function