EasyManua.ls Logo

Samsung DVM S WATER-GEO - Page 92

Samsung DVM S WATER-GEO
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ENGLISH-92
Explanation of optional functions
Flow chart of outdoor unit external contact controller
Indoor unite remote controller ON
2Way solenoid valve On
Pump On
System operation
No
Yes
Flow switch On
System stops
Flow switch detector circuit must be detected for more than 30 seconds within 3 minutes after rst operation signal
output of the pump. (Outdoor unit will not operate when there is no detection.)
Outdoor unit will stop if the contact of ow switch becomes ‘O even during the operation.
When outdoor unit stops, cooling water pump will also stop.
Even when you are not using the external contact control from DVM outdoor unit, you may use other external control
methods such as DDC, PLC or BMS and apply above ow chart. Also apply control for freezing prevention of the water
circulation during winter season.
If you control pump/2way solenoid valve with extra controller, make sure to apply in control so that pump/2way solenoid
valve operates for 3 minutes after the outdoor unit stops operating.

Related product manuals