8-3-9 When the compressor does not operate
1. Checklist :
1) Is the Comp. under the operating conditions? (cooling operating of A, B(C) room)
2) Is the power voltage normal? (the rating voltage ±10% range)
3) Is the connector connection of Comp. good?
4) The Comp. is operated on and off in accordance with the operating conditions of indoor unit of A(B, C) room.
2. Troubleshooting procedure
Comp. A (B) operating conditions
(1) Comp. A : Comp. on /off control in accordance with the A room during the heating and cooling indoor unit operation
(2) Comp. B : Comp. on /off control in accordance with the B(C) room during the heating and cooling indoor unit operation
Comp. A(B) power measuring terminal
(1) Comp. A measuring ; RY73 (4) RY72 (4)
(2) Comp. B measuring ; RY71 (4) RY72 (4)
(3) Power input ; RY72 (3) RY73(3)
*Refer to the power measuring terminal
RED
BLK
RY73
RY71
BLK
RED
WHT
RY72
(3)
(4)
(3)
(4)
(3)
(4)
Keep Comp. off
Normal
Defect of Comp. and running condenser
Replace
Defect of RY72, 73 (Comp. B) and
RY71(Comp. A) contact and coil Replace
Defect of IC06 output
Replace
Defect of IC04 (micom)
Replace
Normal (Comp. off)
Apply the outdoor power and operate the indoor unit A(B,C,D)
in the cooling mode.
Normal
(Comp. off)
Has 3 minutes passed Comp. after the power initial and Comp.
on/off
Is Comp. on?
Is the voltage of pin #14, 13(15) at low
(DC 0.7V)?
Is the voltage of pin #50, 51(52) of IC04 (micom) at
high (DC 5V)?
Is Comp. under the operating condition?
Is the voltage (the rating voltage ±10% range) shown across the
terminal of Comp. power applied?
Is the Comp. under the operating condition?