Feature & Operation
Samsung Electronics78
6-1-7 Indoor fan control in the Heating Mode
Indoor fan is controlled depending on the temperature of indoor heat exchanger in the heating mode.
●
Indoor fan control
The temperature of indoor heat exchanger Indoor fan speed
below 28°Coff
28°C ~ below 34°C LL speed
34°C ~ below 40°C L speed
above 40°C setting speed
When compressor is on
40°C
34°C
28°C
20°C
Setting speed
L Speed
LL Speed
OFF
Compressor
OFF
OFF
UL
ON
When compressor is off
◆ When compressor begins operating
The temperature of indoor heat exchanger Indoor fan speed
above 20°C UL speed
below 20°Coff
after 10 minutes when compressor stops operating off
◆ When compressor stops operating
DB98_20402A(1)_1 10/26/04 2:58 PM Page 78