Operation Instruction & Installation
47Samsung Electronics
Step 4 : Testing operation (Indoor unit)
Step 4 : Press the button.
Step 4 : Result: • The indicator lights on the indoor unit flash at half-second intervals.
Step 4 : Result: • While the indoor unit opens, the indoor unit fan runs to start.
Step 4 : Press the button.
Step 4 :
Result: • The outdoor unit operates in cooling or heating mode as following the room temperature.
Step 4 : Air flow direction - Press the button and check that the air flow blades work properly.
■ Ampere Limit Setting & Changing Procedure
K 1 K 2 K 3
(OFF)
DIS01
SW02 SW01
K 4
DIS02
Outdoor PCB Display
Switch
Indoor unit
address
View data display
Ampere
Switch Selection
34
17.0A
(Default)
ON ON
OFF
ON
OFF
ON
OFF
OFF
14.0A
11.0A
10.0A
• Do not adjust the "Ampere Limit Switch", because it needs to meet HDB requirement or Local authorities.
• "Ampere Limit Switch" is initially set to the 17A.
• "Ampere Limit Switch" is on the PCB of outdoor unit.
• Contact the authorized service technician or dealer for setting and changing the "Ampere Limit Switch".
• Before changing the "Ampere Limit Switch", turn off the main power of the system.
• Please refer to the lower figure and table.