Feature & Operation
Samsung Electronics80
6-1-9 Low Temp. Release
AT COOLING MODE
If the temperature of indoor heat exchanger is below -1°C for over 6minutes, the outdoor fan turns off.
If the temperature of indoor heat exchanger increase over 5°C during the first protection function, the first freezing protection
function is released and the outdoor fan turns on.
If the temperature of indoor heat exchanger increase over 0°C during 6 minutes counting, 6 minutes counter is cleared.
If the temperature of indoor heat exchanger maintains for a minute at -4°C during the 6 minutes counting, switch off the
compressor.
If the compressor is off by Low Temp. Release, 5 minutes release is impossible.
Operation pattern
Indoor Heat exchanger Temp.(˚C)
5[˚C]
0[˚C]
-1[˚C]
6min 6min
6min
COUNT
ON
Low temp.
release
ON
Low temp.
release
OFF
6min
3sec
2sec
ON ONOFF
ON ONOFF
Setting Fan speed Setting Fan speed"LL"
COMP_or
Outdoor FAN
Indoor FAN
*LL = Low FAN speed 35rpm
COUNT
ON
COUNT
ON
DB98_20402A(1)_1 10/26/04 2:58 PM Page 80