20
English
Wired Remote Controller Installation/Service Mode
20
Service Mode
Main
menu
Sub
menu
Function
Data
bit
Factory
setting
Description Unit
6
1 ERV Plus setting/checking
Use of cold air prevention 1 0 0-No use, 1-Use -
Use of humidification when
heating thermo off
2 0 0-No use, 1-Use -
Use of fan operation in
Defrost operation
3 0 0-No use, 1-Use -
Use of humidification when
Heating
4 0 0-No use, 1-Use -
2
ERV Plus set temperature
setting/checking
Cooling 1,2 25 15~30°C 1°C
Heating 3,4 25 15~30°C 1°C
3
ERV Plus Auto mode
temperature setting/
checking
Set temperature 1,2 25 15~30°C 1°C
Set temperature difference 3,4 10 5~15°C 1°C
4
Setting/checking the compensating temperature A
under the Heating EEV control for ERV Plus
1,2 8 0~10°C 1°C
Checking the compensating temperature B under the
Heating EEV control for ERV Plus
30
0 – No use of humidifier(0 °C)
1 – Use humidifier(10 °C)
-
5
ERV Plus fan RPM setting/
checking
Air supply RPM 1,2 - 10~27 Step 1 Step
Air exhaustion RPM 3,4 - 10~27 Step 1 Step
7
1 Status of Automatic Air-Volume setting 1 0
0 - OFF (No use or Cancelled)
1 - Complete(Normal complete)
2 - Running
-
2 Automatic Air-Volume Operation 1 0
0 - Disable(Cancel)
1 - Enable (Running)
-
3 Automatic Air-Volume Voltage Setting 1 2
1 - 220V
2 - 230V (Default)
3 - 240V
-
0 Factory setting 1 0 0 – No use, 1– Factory setting -