EasyManua.ls Logo

Samsung SH09AS2 - Page 58

Samsung SH09AS2
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SAMSUNG | 57
FEATURES & OPERATION
6
Details for Operation Property (cont.)
6-2-11. Overload protection control
AT HEATING MODE
If indoor heat exchanger temp. is over 53°C, outdoor fan turns off.
If indoor heat exchanger temp. is over 60°C, outdoor compressor stops and Indoor fan speed is low.
After compressor and fan are off if indoor heat exchanger temp. is below 50°C, indoor fan and outdoor compressor and outdoor
fan operate normally.
Indoor Heat Exchanger Temp.
60˚C + offset
53˚C + offset
50˚C + offset
Compressor
Outdoor Fan
Indoor Fan
ON
ON
Time
ON
OFF
OFF
Low Speed
3min Delay
2Sec
ON
Setting Speed
offset = 0, 1, 2, 3˚C
DB98_16444A(1)_1 2/9/04 10:04 AM Page 57

Other manuals for Samsung SH09AS2

Related product manuals