SAMSUNG | 57
FEATURES & OPERATION
6
Details for Operation Property (cont.)
6-2-11. Overload protection control
●
AT HEATING MODE
◆ If indoor heat exchanger temp. is over 53°C, outdoor fan turns off.
◆ If indoor heat exchanger temp. is over 60°C, outdoor compressor stops and Indoor fan speed is low.
◆ After compressor and fan are off if indoor heat exchanger temp. is below 50°C, indoor fan and outdoor compressor and outdoor
fan operate normally.
Indoor Heat Exchanger Temp.
60˚C + offset
53˚C + offset
50˚C + offset
Compressor
Outdoor Fan
Indoor Fan
ON
ON
Time
ON
OFF
OFF
Low Speed
3min Delay
2Sec
ON
Setting Speed
✳offset = 0, 1, 2, 3˚C
DB98_16444A(1)_1 2/9/04 10:04 AM Page 57