30 S&C Instruction Sheet 682-510
Maintenance
Figure 53� Lock the outer and low-voltage enclosures�
Padlock
Front
panel
Termination compartment
Returning Equipment to Service
When returning the equipment to service, the following
procedures should be observed:
STEP 1�
Make sure the load-interrupter switch and fault-
interrupter grounding means are removed.
STEP 2� Make certain the load-interrupter switches and
fault interrupters are in the cor rect Open or
Closed positions.
STEP 3�
If a pad-mounted enclosure is furnished, close
and padlock the termination compartment before
energizing the circuit and operating any switch-
ing devices.
STEP 4�
Padlock the switchgear and low-voltage
com partment or enclosure before leaving the
site—even momentarily. See Figure 53. Observe
this procedure even in those cases where the gear
is accessible only to qualied persons.
Operation compartment
Low-voltage
enclosure
Front panel