Thank you for purchasing Santak product.
Observe the warnings on the machine and manual strictly
and properly keep the manual. Do not operate the UPS
before read safety notes and operation instructions.
PDF created with pdfFactory Pro trial version www.pdffactory.com
www.electway.net

Questions and Answers

  • T
    Timothy SummersAug 12, 2025
    Why does my Santak UPS battery discharge time diminish quickly?
    • W
      William CooperAug 13, 2025
      The battery discharge time may diminish because the battery hasn't been fully charged. Keep the UPS connected to utility power persistently for more than 10 hours to charge the battery again. It could also be that the UPS is overloaded, so check the load status and remove any non-critical devices. Finally, the battery may be aged, in which case you should replace it.
  • K
    Kathleen HughesAug 16, 2025
    What to do if the #8 utility power LED blinks on my Santak C3KS UPS?
    • M
      Matthew MitchellAug 16, 2025
      If the #8 utility power LED is blinking, it could be due to a couple of reasons. First, the UPS might be running in battery mode because the voltage or frequency of the utility power is out of the input range. To prevent data loss, save your work and close applications. Ensure that the utility power is within the input voltage frequency range permitted by the UPS. Second, there might be reversed polarity (L,N) of site wiring. In this case, check the polarity of the neutral and line wiring.
  • E
    erica27Aug 20, 2025
    What to do if my Santak C3KS UPS cannot power on?
    • A
      April HamptonAug 20, 2025
      If the Santak UPS doesn't power on, make sure you press the “ON/OFF” button persistently for more than 1 second. Also, check the battery connection, and if the voltage is low, try turning on the UPS without any load.
  • M
    Michelle MurrayAug 25, 2025
    What does it mean when the #1 Fault LED and #2 LED are on and the buzzer beeps continuously on my Santak C3KS UPS?
    • J
      John YorkAug 25, 2025
      This indicates that the UPS is overloaded or the load device is faulty when running on battery. Check the load and remove any non-critical devices. Recalculate the load power and reduce the number of loads connected to the UPS. Also, check whether the load device is faulty.
  • R
    Rebecca TaylorAug 27, 2025
    How to fix Santak C3KS UPS when #1 Fault LED and #6 LED are on and the buzzer beeps?
    • J
      Jillian MillerAug 27, 2025
      The UPS may be overheating. Ensure that the UPS is not overloaded, the ventilation opening is not blocked, and the ambient temperature is not too high. Wait for 10 minutes for the UPS to cool down before turning it on again.
  • J
    Jessica TylerAug 31, 2025
    What to do if the #1 Fault LED and #2 LED and #5 are on, the buzzer beeps continuously on Santak C3KS UPS?
    • C
      Cody WalkerAug 31, 2025
      The UPS output is short circuited. Turn off the UPS and remove all loads. Ensure that the loads are not failed or have no internal short before turning it on again.
  • P
    pbergerSep 3, 2025
    Why is the #10 battery LED blinking on my Santak UPS?
    • W
      Wayne GonzalezSep 4, 2025
      The battery is either not connected or its voltage is too low. Check the battery connection and connect it properly. If the battery is damaged, replace it promptly.
  • J
    Joel MarshallSep 7, 2025
    What does it mean when the utility power is normal but the Santak C3KS UPS cannot run in normal mode?
    • W
      William StewartSep 7, 2025
      The UPS input breaker may be tripped. Reset the input breaker.

Summary

Safety Notes

Operating Safety

Guidelines for safe UPS operation, emphasizing manual reading and adherence.

Electric Safety

Precautions for electrical connections, grounding, and wiring to prevent shock.

Battery Safety

Safety measures for handling UPS batteries, including risks of shock and short circuit.

Installation

Installation Notes

Important considerations and precautions for installing the UPS unit in a suitable environment.

Cable Connection

Guides on connecting input and output cables for UPS, specifying socket requirements.

Operation

Indicators and Modes

Describes LED indicators and introduces UPS operating modes: Normal, Battery, and Bypass.

Operating Instructions

Provides instructions for turning the UPS on and completely powering it down.

Troubleshooting

UPS troubleshooting

Table listing common UPS problems, possible causes, and solutions for fault resolution.

Specifications

Santak C3KS Specifications

General IconGeneral
Input Voltage220/230/240 VAC
Output Voltage220/230/240 VAC
Waveform (Batt. Mode)Pure Sine Wave
Battery Type12V / 9AH
Operating Temperature0-40°C
Weight28 kg
Capacity3000 VA / 2400 W
Frequency50Hz or 60Hz
Transfer Time≤10ms
Typical Recharge Time4 hours recover to 90% capacity
Communication InterfaceRS232, USB
Humidity0-95 % (Non-condensing)
Battery Backup TimeDepends on load
Storage Temperature-15°C to 45°C