W-2WAY ECO-i SYSTEM
Remote Controller Functions
4 - 15
2. Detailed Settings Function
4
DC Fan Tap Change Procedure
<Procedure>
Be sure to turn the main power OFF before performing the steps below.
(1) Check the optional product that will be used from the table below.
Setting No. Optional part name Optional part No.
[1]
Super long-life fi lter AFT-LS140A
Oil guard panel PNR-S140AAG
Ammonia deodorizing fi lter AFT-DS140AG-AM
Optical regeneration deodorizing fi lter AFT-DS140AG-PC
[3]
High-performance fi lter, colorimetric 65% type AFT-MS140A
High-performance fi lter, colorimetric 90% type AFT-HS140A
Air cleaning unit AFT-ES140A
Deodorant fi lter AFT-DS140AG
Air-blocking material (for 3-direction discharge) INS-DS140A
Air-blocking material (when a discharge duct is connected) INS-DS140A
[6] Air-blocking material (for 2-direction discharge) INS-DS140A
Setting No. [1] : Go to (2).
Setting No. [3] : Go to (3).
Setting No. [6] : Go to (4).
(2) Setting No. [1]
Open the cover of the electrical component box, and connect the supplied short circuit connector (2P, YEL) to short-circuit
pin TP1 (2P, RED) on the indoor unit control PCB.
(3) Setting No. [3]
Open the cover of the electrical component box, and connect the supplied short circuit connector (2P, YEL) to short-circuit
pin TP3 (2P, YEL) on the indoor unit control PCB.
(4) Setting No. [6]
Open the cover of the electrical component box, and connect the supplied short circuit connector (2P, YEL) to short-circuit
pin TP6 (2P, WHT) on the indoor unit control PCB.
TP6
White Yellow
Red
TP3 TP1
Indoor unit control PCB
Short-circuit pins (2P)
Also make the appropriate EEPROM settings.